- 摘 要
-
张华栋1, 左中杰1, 郑佳明1, 王 立2, 翟传明1
(1 中电投工程研究检测评定中心,北京 100840;2 中国电子工程设计院,北京 100840)[摘要] 针对医院CT机房CT设备运行时引起的振动问题,通过对其工作区域动力特性的测试,分析振动环境对工作舒适度及楼板结构安全的影响,并在此基础上对CT机房楼板进行减振改造设计。采取在楼板下安装可调节刚度调谐质量阻尼器( TMD)以及粘钢加固措施,既保证了楼板的承载能力,又有效地减小了设备运行引起的振动。可为类似工程振动分析及控制设计提供参考和依据。
[关键词] CT设备;动力特性;减振改造;TMD
中图分类号:TU398 文献标识码:A 文章编号:1002-848X(2012) Sl-0605-04Dynamic analysis and vibration reduction transformation design of CT room floor
Zhang Huadong1, Zuo Zhongjie1, Zheng Jiaming1, Wang Li2, Zhai Chuanming1
(1 C +E Center for Engineering Research Test and Appraisal, Beijing 100840, China; 2 China Electronics Engineering Design Institute, Beijing 100840, China)Abstract: Aimed at the vibration caused by CT eqLupments in CT room of a hospital, through testing the dynanuc response in CT equipments working region, the impact of vibration circumstance on working comfort level and the floor safety was analyzed. The vibration reduction transformation design was made on this basis. By installing adjustable stiffness tuned mass dampers( TMD) and using steel-bonded reinforcement measure, it could guarantee the floor's bearing capacity and reduce effectively the vibration caused by rumung equipment. Reference can be offered for similar project vibration analysis and manage design.
Keywords: CT equipments; dynamic response; vibration reduction transformation; TMD