- 摘 要
-
1)大连理工大学土木水利学院,116024;2)郑州经济开发区质量监督站,450000;3)郑州大学土木工程学院,450002。
【提要】 通过某化工厂服役20年食盐电解车间钢筋混凝土工业厂房的现场测试和构件受力性能的试验研究,对受腐蚀钢筋混凝土构件及结构的可靠度做出了合理的评价,提出不停产、无明火条件下结构的维修加固方案。加固后8年结构运行较好,验证了该加固方案的有效性。
【关键词】 氯离子 腐蚀 钢筋混凝土 加固
Maintenance and Strengthening of Corroded RC Workshops of Chemical Plant/Fan Yingfang1,Zhou Jing2,Huang Bin2,Huang Zhenguo3(1 School of Civil & Hydraulic Eng.,Dalian Univ.of Tech.,Dalian 116024,China;2 Quality Supervising Station of Zhengzhou Economic Development District,Zhengzhou 450000,China;3 School of Civil Eng.,Zhengzhou University,Zhengzhou 450002,China)
Abstract:Field measurements are executed on RC structure of a salt electrolytic plant which has been in service for 20 years.Laboratory experiments on mechanical properties of the corroded RC members are carried out as well.Based on the field test and laboratory experiments,rational safety evaluation is achieved.Retrofitting plan is designed.During the past 8 years,the strengthened structure works well all along,which proves that the retrofitting plan is effective.
Keywords:chloride; corrosion; reinforced concrete; retrofitting