西宁海湖新区财富天街项目商业C3平面超长结构设计与研究
李文华,宫欣
摘 要

(中国建筑技术集团有限公司, 北京 100013)

[摘要]西宁海湖新区财富天街项目商业C3段地上结构平面尺寸大于规范规定的现浇钢筋混凝土框架结构设置伸缩缝的最大间距,通过计算以及裂缝控制措施来分析商业C3段结构超长不设缝是可行的。采用PMSAP软件,进行升温30℃和降温30℃两种工况的应力分析,控制混凝土X向与Y向的平均拉应力均不超过混凝土抗拉强度标准值;根据应力分析结果,对楼板进行加厚、双层双向拉通配筋、提高楼板配筋率;适当提高梁的纵筋配筋率,所有梁的腰筋直径加大一级,保证梁受拉不开裂。采用粉煤灰混凝土,严格控制水灰比在0.50以下,减少水泥用量和用水量,降低水化热和收缩变形;在普通混凝土内滲入水泥用量10%~12%的UEA、HEA等类似膨胀剂,减轻混凝土的开裂。要求施工单位认真做好混凝土的养护,采取有效措施,确保混凝土在湿润的条件下硬化;加强浇水养护,浇水养护时间宜在14d以上。

[关键词]平面结构超长; 温差效应; 裂缝控制

中图分类号: TU318 文献标识码: A文章编号:  1002-848X(2016)S2-0107-04

 

Design and research on C3 building of Xining Haihu New District Fortune Plaza Project

 plane overlength structure

Li Wenhua, Gong Xin

(China Building Technique Group Co., Ltd., Beijing 100013, China)

Abstract: Xining Haihu New District Fortune Plaza Project commercial C3 building was an overlong concrete structure. The structural plane dimension exceeded the maximum size of code requirement, which the plane dimension of cast-in-situ reinforced concrete frame structure should set expansion and contraction joint. Commercial C3 building without the joint is feasible by calculation analysis and crack control measures. A brief description is given on design of overlength structure measure. PMSAP software was adopted to make stress analysis of two operating condition on heating 30℃ and cooling 30℃, average tensile stress of concrete in X and Y direction were controlled not to exceed the value of characteristic value of concrete tensile strength. According to the result, pointed thickening of slab, spreading reinforcement in both two layers and two ways and increasing ratio of reinforcement should be made in slab. In order to ensure no cracks when tension force act on the beam, ratio of longitudinal reinforcement of beam should be increased and diameter of side bar of all the beam be add a level. Fly ash concrete is adopted, water/cement ratio is strictly controlled not to exceed 0.5, decrease cement and water content, and reduce heat of hydration and shrinkage deformation. In order to reduce cracking, expansive admixture as UEA, HEA with a dosage of 10%~12% of cement content. Construction units are requested to do a well concrete maintenance, effective measures should be adopted for concrete hardening under humid conditions; strengthen water curing and time of water curing should be above 14 days.

Keywords: plane overlength structure; temperature variation effect; crack control

 
作者简介:李文华,工程师,Email:aituzi125@163.com。
下载地址

    你还没注册?或者没有登录?这篇论文要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!