Analysis on factors influencing the mathematical formula of strong columnweak beam measures in China
Yang Hong1, Xu Yunzhong2, Sun Yongwei3, Bai Shaoliang1
(1 College of Civil Engineering, Chongqing University, Chongqing 400045, China; 2 Suzhou Tiandi Civil Defence Architecture Design & Research Institute Co., Ltd., Suzhou 215006, China; 3 Chongqing Architecture Design Institute, Chongqing 400015, China)
 
Abstract:Two RC space frames and five RC plane frames in different earthquake intensity regions and with different seismic precautionary criteria were designed according to Chinese code. The influencing laws of the floor location, earthquake intensity region, span of beam, reinforcement of cast-in-place slab and over-reinforced bottom longitudinal bars of beam on the strong column-weak beam measures were discussed based on the calculating results of four types of bending moment ratios of each node. The results show that when formula (6.2.2-1) in Code for seismic design of buildings (GB 50011-2010) was adopted for the strong column-weak beam measures, the effect of reinforcements of cast-in-place slab and over-reinforced bottom longitudinal bars of beam should be considered for the frames in lower earthquake intensity regions, while the effect of reinforcements of cast-in-place slab should be mainly considered for the frames in higher earthquake intensity regions. The influences of earthquake intensity region, floor location and span of beam should be considered when the increase range of reinforcements of cast-in-place slab and over-reinforced bottom longitudinal bars of beam were determined.
Keywords:reinforced concrete; frame structure; strong columnweak beam; moment amplification factor of column end